3.1.11.8 Mains DisconnectThe disconnect option is available in both varieties ofoption cabinets. The position of the disconnect changesbased on the size of the options cabinet and whetherother options are present. Table 3.8 provides more detailabout which disconnects are used.Voltage Frequency convertermodelDisconnect manufacturerand type380–500 V N110T5–N160T4 ABB OT400U03N200T5–N315T4 ABB OT600U03525–690 V N75KT7–N160T7 ABB OT400U03N200T7–N400T7 ABB OT600U03Table 3.8 Mains Disconnect Information3.1.11.9 ContactorA customer-supplied 230 V AC 50/60 Hz signal powers thecontactor.Voltage FrequencyconvertermodelContactormanufacturer andtypeIECutilisationcategory380–500 V N110T5–N160T4GE CK95BE311N AC-3N200T5–N250T4GE CK11CE311N AC-3N315T4 GE CK11CE311N AC-1525–690 V N75KT7–N160T7GE CK95BE311N AC-3N200T7–N400T7GE CK11CE311N AC-3Table 3.9 Contactor InformationNOTICEIn applications requiring UL listing, when the frequencyconverter is supplied with a contactor, the customermust provide external fusing to maintain the UL ratingof the frequency converter and a short circuit currentrating of 100,000 A. Seechapter 5.2.9 Fuseschapter 5.2.10 Fuse Specifications forfuse recommendations.3.1.11.10 Circuit BreakerTable 3.10 provides details on the type of circuit breakerprovided as an option with the various units and powerranges.[V] Frequencyconverter modelCircuit breaker manufacturerand type380–500 N110T5–N132T5 ABB T5L400TWN160T5 ABB T5LQ400TWN200T5 ABB T6L600TWN250T5 ABB T6LQ600TWN315T5 ABB T6LQ800TW525–690 N75KT7–N160T7 ABB T5L400TWN200T7–N315T7 ABB T6L600TWN400T7 ABB T6LQ600TWTable 3.10 Circuit Breaker Information3.1.12 F-frame Panel OptionsSpace heaters and thermostatThere are space heaters mounted on the cabinet interior ofF-frame frequency converters. These heaters are controlledby an automatic thermostat and help control humidityinside the enclosure. The thermostat default settings turnon the heaters at 10 °C (50 °F) and turn them off at 15.6°C (60 °F).Cabinet light with power outletA light mounted on the cabinet interior of F-framefrequency converters increases visibility during servicingand maintenance. The housing includes a power outlet fortemporarily powering tools or other devices, available in 2voltages:• 230 V, 50 Hz, 2.5 A, CE/ENEC• 120 V, 60 Hz, 5 A, UL/cULTransformer Tap Set-upIf the cabinet light & outlet and/or the space heaters &thermostat are installed, transformer T1 requires its taps tobe set to the proper input voltage. A 380-480/500 V drivewill initially be set to the 525 V tap and a 525-690 V drivewill be set to the 690 V tap to ensure no over-voltage ofsecondary equipment occurs if the tap is not changedbefore applying power. See Table 3.11 to set the propertap at terminal T1 located in the rectifier cabinet.Input voltage range Tap to select380 V-440 V 400 V441 V-490 V 460 V491 V-550 V 525 V551 V-625 V 575 V626 V-660 V 660 V661 V-690 V 690 VTable 3.11 Transformer Tap SetupSelection Design GuideMG16C202 Danfoss A/S © Rev. 05/2014 All rights reserved. 593 3