Par. No. # Parameter description Default value 4-set-up Change duringoperationConver-sion indexType26-0* Analog I/O Mode26-00 Terminal X42/1 Mode [1] Voltage All set-ups TRUE - Uint826-01 Terminal X42/3 Mode [1] Voltage All set-ups TRUE - Uint826-02 Terminal X42/5 Mode [1] Voltage All set-ups TRUE - Uint826-1* Analog Input X42/126-10 Terminal X42/1 Low Voltage 0.07 V All set-ups TRUE -2 Int1626-11 Terminal X42/1 High Voltage 10.00 V All set-ups TRUE -2 Int1626-14 Term. X42/1 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int3226-15 Term. X42/1 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int3226-16 Term. X42/1 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint1626-17 Term. X42/1 Live Zero [1] Enabled All set-ups TRUE - Uint826-2* Analog Input X42/326-20 Terminal X42/3 Low Voltage 0.07 V All set-ups TRUE -2 Int1626-21 Terminal X42/3 High Voltage 10.00 V All set-ups TRUE -2 Int1626-24 Term. X42/3 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int3226-25 Term. X42/3 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int3226-26 Term. X42/3 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint1626-27 Term. X42/3 Live Zero [1] Enabled All set-ups TRUE - Uint826-3* Analog Input X42/526-30 Terminal X42/5 Low Voltage 0.07 V All set-ups TRUE -2 Int1626-31 Terminal X42/5 High Voltage 10.00 V All set-ups TRUE -2 Int1626-34 Term. X42/5 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int3226-35 Term. X42/5 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int3226-36 Term. X42/5 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint1626-37 Term. X42/5 Live Zero [1] Enabled All set-ups TRUE - Uint826-4* Analog Output X42/726-40 Terminal X42/7 Output [0] No operation All set-ups TRUE - Uint826-41 Terminal X42/7 Min. Scale 0.00 % All set-ups TRUE -2 Int1626-42 Terminal X42/7 Max. Scale 100.00 % All set-ups TRUE -2 Int1626-43 Terminal X42/7 Output Bus Control 0.00 % All set-ups TRUE -2 N226-44 Terminal X42/7 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint1626-5* Analog Output X42/926-50 Terminal X42/9 Output [0] No operation All set-ups TRUE - Uint826-51 Terminal X42/9 Min. Scale 0.00 % All set-ups TRUE -2 Int1626-52 Terminal X42/9 Max. Scale 100.00 % All set-ups TRUE -2 Int1626-53 Terminal X42/9 Output Bus Control 0.00 % All set-ups TRUE -2 N226-54 Terminal X42/9 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint1626-6* Analog Output X42/1126-60 Terminal X42/11 Output [0] No operation All set-ups TRUE - Uint826-61 Terminal X42/11 Min. Scale 0.00 % All set-ups TRUE -2 Int1626-62 Terminal X42/11 Max. Scale 100.00 % All set-ups TRUE -2 Int1626-63 Terminal X42/11 Output Bus Control 0.00 % All set-ups TRUE -2 N226-64 Terminal X42/11 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint166.2.22. 26-** Analog I/O Option MCB 1096. How to programme the frequency converter VLT® HVAC Drive Operating Instructions118 MG.11.A4.02 - 09.10.06. VLT® is a registered Danfoss trademark6