7.3.2 Bytes 2–3: Starter StateBits Details0–3 The decimal value of bits 0–3 indicates the soft starter’sstate:0 = Communication error between device and soft starter.1 = Ready.2 = Starting.3 = Running.4 = Stopping.5 = Not ready (restart delay, restart temperature check).6 = Tripped.7 = Menu open (cannot start).8 = Jog forward.9 = Jog reverse.4 0 = Negative phase sequence.1 = Positive phase sequence.5 1 = Current exceeds FLC.6 0 = Uninitialized.1 = Initialized.7 1 = Communication error between device and soft starter.8–15 Reserved.Table 7.3 Description of Bytes 2–37.3.3 Bytes 4–5: Trip CodeBits Details0–15 See chapter 7.5 Trip Codes.Table 7.4 Description of Bytes 4–57.3.4 Bytes 6–7: Motor CurrentBits Details0–15 Average rms current across all 3 phases.Table 7.5 Motor Current7.3.5 Bytes 8–9: Motor TemperatureBits Details0–15 Motor 1 thermal model (%).Table 7.6 Description of Bytes 8–97.3.6 Bytes 10–59: Extended InformationByte Description Bits Details10–11 Version 0–5 Reserved.6–8 Product parameter list version.9–15 Product type code4 = MCD 2007 = MCD 50012–13 Device detailsByte Description Bits Details14–15 Reserved16–17 Reserved18–19 Soft starter state 0–4 0 = Reserved.1 = Ready.2 = Starting.3 = Running.4 = Stopping.5 = Not ready (restart delay,restart temperature check).6 = Tripped.7 = Programming mode.8 = Jog forward.9 = Jog reverse.5 1 = Warning.6 0= Uninitialized.1 = Initialized.7 0 = Hand On.1 = Auto On.8 Reserved.9 0 = Negative phase sequence.1 = Positive phase sequence.10–15 See chapter 7.5 Trip Codes.20–21 Current 0–13 Average current across all 3phases.14–15 Reserved.22–23 Current 0–9 Current (% of FLC).10–15 Reserved.24–25 Motortemperature0–7 Motor 1 thermal mode (%).8–15 Motor 2 thermal mode (%).26–27 Power1) 0–11 Power.12–13 Power scale.14–15 Reserved.28–29 % Power factor 0–7 100% = power factor of 1.8–15 Reserved.30–31 Reserved32–33 Current 0–13 Phase 1 current (rms).14–15 Reserved.34–35 Current 0–13 Phase 2 current (rms).14–15 Reserved.36–37 Current 0–13 Phase 3 current (rms).14–15 Reserved.38–39 Reserved40–41 Reserved42–43 Reserved44–45 Parameter listversion number0–7 Parameter list minor version.8–15 Parameter list major version.46–47 Digital inputstate0–15 For all inputs, 0 = open, 1 =closed (short-circuited).0 = Start.1 = Stop.2 = Reset.3 = Input A.4–15 = Reserved.48–49 Trip code 0–15 See chapter 7.5 Trip Codes.Packet Structures Installation GuideMG17P102 Danfoss A/S © 11/2017 All rights reserved. 137 7