Danfoss Drives · DKDD.PB.551.A1.02 | 13• The soft starter’s current rating at the required start duty must be at least equal to themotor’s nameplate rating. If the motor’s nameplate rating is not available, approximateinformation is available from the following table.Motor Power Current rating at different voltageskW HP 220-230 V 380-400 V 440 V 500 V 660-690 V7.5 10 27 15.5 13.7 12 8.911 15 39 22 20.1 18.4 1415 20 52 30 26.5 23 17.318.5 25 64 37 32.8 28.5 21.322 30 75 44 39 33 25.425 35 85 52 45.3 39.4 30.330 40 103 60 51.5 45 34.637 50 126 72 64 55 4245 60 150 85 76 65 4955 75 182 105 90 80 6175 100 240 138 125 105 8290 125 295 170 146 129 98110 150 356 205 178 156 118132 180 425 245 215 187 140140 190 450 260 227 200 145147 200 472 273 236 207 152150 205 483 280 246 210 159160 220 520 300 256 220 170185 250 595 342 295 263 200200 270 626 370 321 281 215220 300 700 408 353 310 235250 340 800 460 401 360 274257 350 826 475 412 365 280280 380 900 510 450 400 305295 400 948 546 473 416 320300 410 980 565 481 420 325315 430 990 584 505 445 337335 450 1100 620 518 472 355355 480 1150 636 549 500 370375 500 1180 670 575 527 395400 545 1250 710 611 540 410425 580 1330 760 650 574 445445 600 1400 790 680 595 455450 610 1410 800 690 608 460475 645 1490 850 730 645 485500 680 1570 900 780 680 515560 760 1750 1000 860 760 570600 800 1875 1085 937 825 625650 870 2031 1176 1015 894 677700 940 2187 1266 1093 962 729750 1000 2343 1357 1172 1031 781800 1070 2499 1447 1250 1100 833850 1140 2656 1537 1328 1168 885900 1250 2812 1628 1406 1237 937950 1275 2968 1718 1484 1306 9891000 1340 3124 1809 1562 1375 1041Note: Information is based on a 4-pole motorSoft Starter Sizing