Table 35: 33-2 - Start Pressure LevelRange Function* 5 1–5000 Sets the pressure level to trigger the soft starter to perform a soft start.Table 36: 33-3 - Start Response DelayRange Function* 0.5 s 00:00:100–30:00:000mm:ss:msSets a delay between the pressure passing the pressure control start level and the soft starter per-forming a soft start.Table 37: 33-4 - Stop Pressure LevelRange Function* 10 0–5000 Sets the pressure level to trigger the soft starter to stop the motor.Table 38: 33-5 - Stop Response DelayRange Function* 0.5 s 00:00:100–30:00:000mm:ss:msSets a delay between the pressure passing the pressure control stop level and the soft starterstopping the motor.6.5.2.5 Parameter Group 36-** Pump Trip ActionTable 39: 36-1 - Pressure SensorOption FunctionSelects the soft starter's response if it detects a fault with the pressure sensor.* Soft and Trip LogSoft Trip and ResetTrip StarterTrip and ResetWarn and LogLog Only6.6 Depth ProtectionDepth protection uses terminals B13, B14 or C13, C14 on the smart card.• B13, B14: Use an analog 4–20 mA sensor.• C13, C14: Use a normally open digital switch sensor.Depth protection is always active (ready, start, run, and stop modes).The smart card trips the soft starter when the depth level passes through the programmed trip level. The trip cannot be reset until thedepth has returned above the reset level (parameter 34-2 Depth Reset Level).ConfigurationInstallation Guide | Pumping Smart CardAN279052730268en-000102 / 175R118324 | Danfoss A/S © 2018.10