18Mounting and installationSuspension The wall suspension bar supplied with the unit is fixed to the wall and the dehumidifieris hung up on it. It is important to mount the unit in a horizontal position to secure cor-rect outflow of the condensate water.The dehumidifier must be placed in a way that allows unimpeded air intake through thefront and outlet through the grill on the sides. Be sure always to leave at least 100 mmfree space around the unit for optimum operation.It is important that the dehumidifier is not installed near a source of heat as for exam-ple a radiator, and doors and windows must be kept closed when the dehumidifier is infunction.Installation of thewater tank1. Place the CDF 10 on the wall by means of the wall suspension bar.2. Then dismantle the front panel of the CDF 10.3. Fix the water container cabinet by 4 machine screws under the bottom of theCDF 10.4. Take the supply cable through the diaphragm bush at the bottom of the watertank cabinet.5. The control of the CDF 10 is placed in a box behind the front panel. To get ac-cess to the control, unscrew the 4 screws on the sides of the box and removethe box lid.6. Take the cable from the magnetic switch through the diaphragm bush at thebottom of the CDF 10 and connect it to the terminal strip on the PCB – terminalpoints 13/14 (WATER SW).7. Remount the control box lid and the front panel.8. Place the water tank in the water tank cabinet. The float must be turned to-wards the magnetic switch.Drawing The water tank is mounted beneath the CDF10 as shown on the drawing:Continued overleaf