53Operation |Table 7. Settings (continued)Description Default SettingAvailable SettingsClear Event Log The number after “Total events” shows howmany events are currently stored in the log.Press the button for longer than onesecond to reset the event count to zero andclear the log.—LCD Contrast [-5], [-4], [-3], [-2], [-1], [+0], [+1], [+2], [+3],[+4], [+5]The LCD Contrast is adjustable from -5 to +5. Thisrange covers the maximum adjustment forcontrasting the background with the text in thevisual display of the control panel.+0Transferring the UPS Between ModesTransferring between modes includes: Transferring from Normal to Bypass mode Transferring from Bypass to Normal modeTransferring from Normal to Bypass ModeTo transfer from Normal to Bypass mode:1 Press the button for longer than one second to go to the main menu selection and scroll down tothe Control menu using the button.2 Press the button to enter the Control menu.3 Select Go to Bypass.The text on the screen changes to Manual Bypass Command Sent. The Bypass mode iconflashes, indicating Bypass mode.