AH5 00 Hardw are Manu alError Description Remedycode16#823CThe CPU parameterdownloaded is incorrect.The UDP socket is setincorrectly.1. Check the Ethernet parameter in the CPUmodule in HWCONFIG.2. Check whether the version of HWCONFIG usednow is compatible with the version of the CPU.9.1.3 BUS FAULT LED Indicator’s Being ONWhen a CPU module detects an error, the BUS FAULT LED indicator on the CPU module is ON.The BUS FAULT LED indicator on the CPU module corresponds to the ERROR LED indicator on anI/O module. If an error occurs in an I/O module, the status of the BUS FAULT LED indicator on theCPU module is the same as that of the ERROR LED indicator on the I/O module. If there are errorsoccurring in the I/O modules, the BUS FAULT LED indicator on the CPU module will be ON. Forexample, the BUS FAULT LED indicator on the CPU module will be ON if the ERROR LED indicatoron I/O module A is ON and the ERROR LED indicator on I/O module B blinks. If the ERROR LEDindicator on I/O module B still blinks after the error occurring in I/O module A is eliminated, the BUSFAULT LED indicator on the CPU module will blink. Please refer to sections 12.4.2~12.4.8 in AH500Operation Manual for more information about the LED indicators.Users can get the remedies for the errors detected by a CPU module from the table below. If theerror code which users get is not listed in the table below, users need to check whether the I/Omodule operates normally. Please refer to section 9.2 in this manual for more information about thetroubleshooting for I/O modules.Errorcode Description Remedy16#0013 The I/O module can notrun/stop. (SM10)Check whether the setting of the parameter for themodule is correct. If the setting is correct, pleasecheck whether the module breaks down. If the errorstill occurs, please contact the factory.16#0014The procedure of restoring thesystem can not be executed.(SM9)The contents of the system backup file areincorrect, or the file does not exist in the pathspecified. If the file exists and the procedure ofrestoring the system can not be executed, pleasebacking up the system again. If the error stilloccurs, please contact the factory. (Please refer tosection 7.5 in AH500 Operation Manual, andsection 18.2 in ISPSoft User Manual for moreinformation about the memory card.)16#1400An error occurs when the datais accessed through theauxiliary processor. (SM9)Please contact the factory.16#1401An error occurs when the datain the I/O module is accessed.(SM9)Please contact the factory.16#1402The actual arrangement of theI/O modules is not consistentwith the module table. (SM9)Check whether the module table in HWCONFIG isconsistent with the actual arrangement of the I/Omodules.16#1403An error occurs when the datais read from the module.(SM9)Check whether the module operates normally. If theerror still occurs, please contact the factory.16#1404 A watchdog timer error occursin the module. (SM9)Check whether the module breaks down. If themodule breaks down, please replace it and contactthe factory.16#1405 The setting parameter of themodule is not found. (SM9)Set the parameter in HWCONFIG again, anddownload it.9 - 1 0