Product Manual Oria ThermostatEAE KNX Oria Thermostat Oria Thermostat PM R1.0©EAE Technology www.eaetechnology.com Sayfa 49 / 504.6 StatusFigure 264.6.1 ParametersStatus parameter can be used to enable/disable additional control mode status telegrams. Status telegramsoperate the same way as switchover telegrams. But instead of sending switchover telegrams as DPT 1.100 orDPT 20.105, sends 1 bit On/Off (DPT 1.002) telegrams.Parameter Setting DescriptionHeating Status Enable / Disable Enable additional heating statuscommunication object.Cooling Status Enable / Disable Enable additional cooling statuscommunication object.Table 514.6.2 Communication ObjectsNo Object Name Function Data Types Flags64 Status Heat On/Off 1 bitDPT 1.002CRTHeating status will be send through this communication object. (0 : Heating Off, 1 : Heating On)65 Status Cool On/Off 1 bitDPT 1.002CRTCooling status will be send through this communication object. (0 : Cooling Off, 1 : Cooling On)Table 52