Page 159130 UPS-ENENGLISH4. OperationThe table 4 shows the basic menu structure.Table 4. Menu Map for Display FunctionsMain Menu Submenu Display Information or Menu FunctionUPS Status Main status (mode and load) / Notice or Alarm status(if any) / Battery status (state and charge level)Event Log Displays up to 127 events and alarms.The Event Log is also available through the serial port. See"Retrieving the Event Log" on page 19.Measurements Load W VA / Load A pf / Output V Hz / Input V Hz / Bypass V Hz /Input Line Events / Battery V minControl Go to Bypass Transfers the UPS system to internal Bypass mode.When this command is active, the option changes to "Go toNormal".Start Battery Test Starts a manual battery test.See "Testing New Batteries" on page 29.Reset Error State Clears a "Battery Test Failed" alarmRestore Factory Settings Returns all settings to original valuesIdentification UPS Type / Part Number / Serial Number / FirmwareSettings User Settings See Table 5 for details.Service Settings This menu is password-protected.User SettingsThe following table displays the options that can be changed by the user.Table 5. User SettingsDescription Available Settings Default SettingChange Language [English] [French] [Spanish] [German] [Russian]Menus, status, notices, and alarms are in allsupported languages. UPS faults, Event Log data,and settings are in English only.EnglishUser Password [Enabled] [Disabled]If Enabled is selected, the password is USER.DisabledAudible Alarms [Enabled] [Disabled] EnabledSet Date and TimeNOTE: time is a 24-hourclock.Set Year, Month, Day, Hours, MinutesDate: yyyy/mm/ddTime: hh:mm2008/01/0112:00Signal Inputs Setup: [Not Used] [Force Bypass] [RemoteShutdown] [Delayed Shutdown][On Generator] [Building Alarm 1]Active: [High] [Low]See "Programmable Signal Inputs" on page 24.RS232-3: Not Used, HighcXSlot Serial: DelayedShutdown, HighcXSlot Signal: RemoteShutdown, LowRelay Configuration [UPS ok] [On Bypass] [On Battery] [Battery Low][Ext. Charger On]See "Relay Output Contacts" on page 23.Standard: UPS okRS232-1: Battery LowRS232-8: On BatterycXSlot-K1: On BatterycXSlot-K2: Battery LowcXSlot-K3: UPS okcXSlot-K4: On BypassSerial Port Configuration [1200 bps] [2400 bps] [9600 bps]NOTE: USB communication requires 9600 bps.RS232: 9600 bpscXSlot: 9600 bpsControl Commands fromSerial Port[Enabled] [Disabled] RS232: EnabledcXSlot: EnabledOutput Voltage [208V] [220V] [230V] [240V] [Autosensing] 230 VOutput Frequency [50Hz] [60Hz] [Autosensing] AutosensingFrequency Converter [Enabled] [Disabled]If Enabled, the UPS operates as a frequencyconverter, with bypass operation and all bypass-related alarms disabled.DisabledOverload Alarm Level [10%] [20%] [30%] ... [100%]These values affect alarm level only, not UPSoperation such as transfers or shutdown.100 %Generates the Output.Overload alarm at the setlevel.Transfer to Bypass WhenOverload*[Immediate] [After Delay]If Immediate, transfer occurs at load > 102 %.If After Delay, transfer occurs according to table 20on page 32.After Delay