Page 16 9130 UPS-EN4. OperationPower Strategy [Normal] [High Efficiency]See "Setting Power Strategy" on page 19.NormalAutomatic start delay [No Delay] [Disabled] [1,2,...,32767 s]To define if the load turns automatically on, withthe delay set after the utility return, if it has beenshutdown by:- signal input with auto-restart option- an XCP command with autorestart option- battery under voltage state, or automatic onbattery shutdown command.No DelayAutomatic on batteryshutdown[Disabled] [No Delay] [1,2,...,32767 s]To define if the load turns automatically off when"UPS on battery" state activates.DisabledStart on BatteryNOTE: utility must bepresent and outputenabled at initial UPSstartup.[Enabled] [Disabled]After initial startup, battery voltage must exceed2.10 volts per cell to start on battery.EnabledEnergy Saving Mode [Disabled] [50W] [100W] ... [1000W]UPS output is turned off (after 5 min) if the UPS ison battery and output power is below the selectedlevel.DisabledRemote Shutdown Delay [No Delay] [1s] [2s]...[10800s] No DelayDelayed Shutdown Delay [No Delay] [1s] [2s]...[10800s] 120 sOn Battery Notice Delay [0] [1s] [2s]...[99s] 5 sSite Wiring Fault Alarm [Enabled] [Disabled]An active site wiring fault alarm prevents startup or,if operating, forces operation to Battery mode anddisables bypass.EnabledBypass Voltage LowLimit*[-4%] [-5%] ... [-20%] of nominal -15 % of nominalBypass Voltage HighLimit*[+4%] [+5%] ... [+20%] of nominal +10 % of nominalQualify Bypass* [Never] [When in Spec] [Always on UPS Fault][Always]When in SpecSynchronization Window* [Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±2.0 Hz][±3.0 Hz]±3 HzUnsynchronizedTransfers*[Enabled] [Disabled] EnabledNumber of Battery Strings [0] [1] [2] ... [10]See "Configuring the UPS for EBMs" on page 18.1Battery Charge Mode [ABM Cycling] [Constant] ABM CyclingTemperatureCompensated Charging[Enabled] [Disabled]If Disabled, the default charger voltages for 25 °C(77°F) are assumed.EnabledBattery Charge % toRestart[Not Checked] [10] [20] ... [100]If a percentage is selected, automatic restart (ifenabled) occurs when the battery’s charge reachesthe selected level.Not CheckedBattery Low Alarm [Immediate] [2 min] [3 min] [5 min]The "Battery Low" alarm triggers when the setamount of backup time (approximately) remains inthe batteries. If set to Immediate, the alarm activatesat the same time as the "UPS on Battery" notice.3 minAutomatic Battery SupportTests[Enabled] [Disabled]See "Running Automatic Battery Tests" on page 20EnabledDeep discharge protection [Enabled] [Disabled]Protection against deep discharge. If disabled, Eatonwarranty will be void.EnabledStart on Bypass [Disabled] [Enabled]During start up sequence, transfer first on Bypass(for 5~15 seconds) then transfer online.DisabledAmbient TemperatureWarning[Enabled] [Disabled] EnabledPredictive MaintenanceNotices[Enabled] [Disabled] EnabledRemote Power-off (RPO)Input Polarity[Open] [Closed] Open* See "Configuring Bypass Settings" on page 19.