POWER WIRING INSTALLATION NOTES071608C15 of 23DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:164201603-6INSTALLATION INFORMATIONEaton®9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual 164201603 Rev 4 www.eaton.com/powerquality A-2714. External overcurrent protection is not provided by this product, but is required by codes.Refer to Table F through Table K for wiring requirements. If an output lockable disconnectis required, it is to be supplied by the user.15. Table P lists the maximum rating for input circuit breakers. When wiring a single‐feed input,the rating requirements for the input circuit breakers are superceded by the ratings listedin Table Q.Table P. Maximum Input Circuit Breaker RatingsUPS Model Input Voltage Rating% Rating 208V/220V 380V 400V 415V 480VPowerware9390/9390IT-40/2080% 90A 50A 50A 45A 45A100% 70A 40A 40A 35A 35APowerware9390/9390IT-40/3080% 125A 70A 70A 60A 60A100% 100A 60A 60A 50A 45APowerware9390/9390IT-40/40Powerware 9390-80/4080% 175A 90A 90A 80A 70A100% 150A 80A 80A 70A 60APowerware 9390-80/50 80% 225A 110A 110A 100A 100A100% 175A 90A 90A 90A 80APowerware 9390-80/60 80% 250A 150A 125A 125A 125A100% 200A 110A 110A 100A 90APowerware 9390-80/80 80% 350A 175A 175A 175A 150A100% 300A 150A 150A 150A 125AC A U T I O NTo reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table P inaccordance with the National Electrical Code, ANSI/NFPA 70.16. Source protection for the AC input to bypass should be treated as if supplying an 80 kVAthree‐phase transformer, to allow for inrush current if an IDC with a transformer is installed.Bypass input wiring and bypass input breaker rating should be treated as if supplying an80 kVA load, regardless of the rating of the UPS.17. The line‐to‐line unbalanced output capability of the UPS is limited only by the full loadper phase current values for AC output to critical load shown in Table F through Table K.The recommended line‐to‐line load unbalance is 50% or less.