USING THE CONTROL PANELEaton®9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual 164201603 Rev 4 www.eaton.com/powerquality 8-38.2 Using the Main MenuThe UPS main menu bar allows you to display data in the information area to help youmonitor and control UPS operation. The following menus and options are available:Menu Option DescriptionEVENTS Displays the list of Active System Events and a historical log of system events.METERS Displays performance meters for the system or critical load.CONTROLS Displays the System Controls screen.SETUP Allows you to set the display contrast, set the date and time for the time stamp,configure the UPS serial communication ports, and view the firmware version numbers.LOAD OFF De-energizes the critical load and powers down the UPS.Returns to Main Menu and Mimic screen from the Events, Meters, Controls, or Setupscreens. Returns to the main System Setup Level screen from a setup submenu.8.2.1 Mimic ScreenFigure 8‐3 shows the Main Menu and Mimic screen. To select the Mimic screen fromthe Events, Meters, Controls, or Setup screens, press the pushbutton on thecurrent menu bar.The Mimic screen shows the internal components of the UPS cabinet and a real‐timegraphical representation of the operating status of the system.In Energy Saver mode, all Mimic lines show as active (double lines). If the inputbreaker is opened or the input feed is out of limits, the input will show as a single line.TIME: 11 : 35 : 43 DATE: 02 / 25 / 2004CONTROLS LOAD OFFMETERSEVENTS SETUPOUTPUTBATTUPSINPUTSTSWBYPASSFigure 8‐3. Main Menu and Mimic Screen (Normal Mode)