Eaton 93E UPS 15-80 kVA (380/400/415 V) Installation and Operation Manual© Eaton Corporation plc 2015. All rights reserved. Revision: 001 Document ID: 614-01975-00 68 (133)4. Remove the small parts from the knockout in the right side plate.5. Route and install the RJ-45 Controller Area Network (CAN) cablesbetween the UPS cabinets. See Figure 20, Figure 24 and Figure 25for wiring information.6. Route and install pull chain wiring (twisted wires 0.5-2.0 mm2)between the UPS cabinets and cabinet MOBs. See Figure 20,Figure 24 and Figure 26 for wiring information.7. Anchor the cabling to the UPS door.8. If you are wiring MiniSlot connections, proceed to Section 5.6.1.5.6.1 Installing MiniSlot interface connectionsNOTE: The LAN drop for connection to the UPS communications cardis to be supplied by the customer.For installation and setup of a MiniSlot card, contact an Eaton servicerepresentative (see Section 2.7)To install wiring:1. If not already installed, install the LAN drop.2. Route and install the LAN and other cables to the appropriateMiniSlot cards. See Figure 19 and Figure 20 for the MiniSlotcommunication bay locations.3. Anchor the cabling to the UPS door.4. Refer to the manual supplied with the MiniSlot card for operatorinstructions.5. Install the power terminal cover using the provided hardware.5.7 Installing a remote EPO switchA latching-type remote Emergency Power-off (EPO) switch can be usedin an emergency to shut down the UPS and remove power to the criticalload from a location away from where the UPS is installed.