80Please refer to the following table for conductor’s terminal selection:Recommended circuit breaker and contactor current specifications:Model name Input mode Breaker Contactor9SX 15KPM(AU)DXRT 15KS-IN1 phase main input D type 125A ≥125A3 phase main input D type 63A ≥63A1 phase bypass input D type 100A ≥100A3 phase bypass input D type 40A ≥40A9SX 20KPM(AU)DXRT 20KS-IN1 phase main input D type 160A ≥160A3 phase main input D type 63A ≥63A1 phase bypass input D type 125A ≥125A3 phase bypass input D type 63A ≥63ARecommended output circuit breaker current specifications:Model name Output mode Breaker current9SX 15KPM(AU)DXRT 15KS-IN1 phase output 100A3 phase output 40A9SX 20KPM(AU)DXRT 20KS-IN1 phase output 125A3 phase output 63ANote: The diameter and cross-section of the cable conductor depend on therated power of the UPS. The above wire diameter is for user's reference only.Conductor cross-section (Unit:mm²) Ring terminal type6 DRNB6-610 DRNB6-1016 DRNB8-1625 DRNB8-2535 DRNB8-3550 DRNB8-50