0359-CPR-004192. Connection details1a. Mounting base (IP21C) 1b. Mounting base (IP66C)Table 1. SpecificationTechnical data Effective September 2014FXN009SB/EF009SBFXN009SBWP/EF009SBWPFXN009/EF009FXN009WP/EF009WPWall sounder/beaconWall sounderSupply voltage (BiWire alarm) 25.5~35 VdcSupply voltage (BiWire standby) 18~25.5 VdcSupply voltage (conventional) 18~35 VdcCable size/type 0.5~2.5mm/FIRETUF, FP200or MICCStandby current (BiWire mode) <15μACurrent (high volume) Sdr only = 4.7mA, AV = 11mACurrent (low volume) Sdr only = 2.6mA, AV = 8.7mASound output (high volume) 99 +/- 3dB(A) : All tonesSound output (low volume) 89 +/- 3dB(A) : All tonesOperating temperature -25 to +70ºC (93% ± 3%RH)Material ABS FR plasticEnvironmental category Type A= IP21C/ Type B= IP66Tones 3, See section 3Flash rate 0.5Hz (N/A to FXN009(WP), EF009(WP))Flash on period 60ms (N/A to FXN009(WP), EF009(WP))Feature Value Feature ValueBiWire Ultra range:Wall sounder/beacon IP66Wall sounder IP66505060(i) Drill required holes forcable gland fixing.(iii) Fix to mounting surfaceusing two suitable screws.(ii) Drill out the requiredfixing holes.Drill position for rearcable entryDrill position forglands50 (IP33)50 (IP33)75 (IP66)97 (IP66)62 (IP33)(i) Drill required holes for cable gland fixing (top or bottom)and ensure cables are correctly sealed for IP66 integrity.(ii) Fix to mounting surface using four suitable screws.Drill positionfor glandsUse these four holesto ensure IP66 integrity1 2 3 4 51OnOff3. Switch position meaning1, Sounder on/off (AV version only)2, Volume high (Off)/low (On)3, Tones4, Tones5, Mode: On = BiWire, Off = ConventionalContinuous: 3=On, 4=On (984Hz)Bell: 3=On, 4=Off (1440Hz)Alternating: 3=Off, 4=On (644/984Hz){OUT INSCREEN ZONE OUT ZONE IN+VE -VE +VE -VEZONE INZONE OUTScreen must be continuous along entire length of loop.Compliance EN54-3; EN54-23:201014(Conventional compatible)25-12766-E2NoteAll products meet minimum requirements of IP33C inaccordance with EN54-3.www.acornfiresecurity.comwww.acornfiresecurity.com