Effective July 2010Supersedes April 2010Installation Leaflet IL04209006EPROFIBUS Module for use withMotor Insight, C440 and S611InstallationThe PROFIBUS module is designed to be used inindustrial applications and installed in accordancewith this document.Mount the ModuleTo mount the PROFIBUS adapter to MotorInsight® or C440-COM-ADP the following pro-ceedure must be preformed.• Place the tabs opposite the PROFIBUS con-nector into the lower slots provided on theMotor Insights right side.• Pivot the module on the lower tabs towardthe Motor Insight.• Gently press the module and Motor Insighttogether.Connect the PROFIBUS Adapter to PROFIBUSConnect the PROFIBUS terminal to the PROFIBUSDB9 connector located on the side of the module.The connector has screws for positive retention toeliminate accidental unplugging.Connect 24 Vdc control power to the 5-positionheader.• The connector has screws for positive reten-tion to eliminate accidential unplugging.• Use one wire per terminal.Set the PROFIBUS addressThe PROFIBUS address is set using the DIPswitches located on the face of the module. ThePROFIBUS address is binary with the major unitsnumbered to the left of the switch on the sidelabel. Adding up the major units set to ON deter-mines the address of the module.Example: To set the address to 25, start from theswitch mark 32 and set the switches to Off (32),ON (16), ON (8), OFF (4), OFF (2) ON (1) (16+8+1=25).Note: Address is only updated upon power up.The PROFIBUS baud rate is set automaticallyusing an auto baud technology, there is no needto set the baud rate. For more information on thePROFIBUS attributes and how to modify them,refer to the appropriate user manual. Motor InsightMN04209001E, C440 MN04201001E or S611MN03902011E.The GSD file is located on the Eaton web site, goto www.eaton.com.C441S - 120 Vac Input SpecificationSpecification ValueNumber of Inputs 4Nominal Voltage 120 VacNominal Current 15mAOperating Frequency 50/60HzSignal Delay max. 30msInput type IEC 61131-2Type 1 DigitalC441Q - 24 Vdc Input Specification