Configuration Using the PROFIBUS Configuration File20 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.comEnable Phase Reversal trip S611 0 = disable fault1 = enable faultEnable Overload on start trip S611 0 = disable fault1 = enable faultEnable Shorted SCR trip S611 0 = disable fault1 = enable faultEnable SCR Not Firing trip S611 0 = disable fault1 = enable faultEnable Over Temp trip S611 0 = disable fault1 = enable faultEnable GND Fault trip S611 0 = disable fault1 = enable faultJam Trip Level S611 Current threshold setting for Jam fault. (valid only during bypass 150–400% rated motor fla)Jam Trip Delay S611 Length of jam condition before fault in sec. (1–20)Stall Trip Level S611 Current threshold setting for Stall fault. (valid only at end of start ramp 150–300% rated motor fla)Residual GF Trip Level S611 Current threshold setting for GND fault trip. (in 0.1A) (1–100)Residual GF Trip Delay S611 Length of GND fault condition before fault in sec. (1–20)Residual GF Start Delay S611 Length of time from start to mask fault. (0–20sec)Current Unbalance Trip Level S611 Current Imbalance fault threshold. (1–20%)Current Unbalance Trip Delay S611 Length of current imbalance condition before fault. (1–20sec)Load Disconnect Trip Level S611 Load disconnect fault threshold. (% motor fla: 1–50%)Load Disconnect Trip Delay S611 Length of load disconnect condition before fault. (1–60sec)Load Disconnect Source S611 Low PowerLow CurrentPhase Loss Trip Level S611 Phase loss fault threshold. (% motor fla: 0–100%)Phase Loss Trip Delay S611 Length of phase loss condition before fault. (1–20sec)Start Control Level or Edge S611 S611 input configuration0 = Edge triggered inputs1 = Level triggered inputsFault Relay Configuration S611 S611 fault relay configuration—relay output enabled when:0 = Faulted1 = Not FaultedAux Relay Configuration S611 S611 aux relay configuration—relay output enable when:0 = Faulted1 = Not Faulted2 = in Bypass3 = Not in Bypass4 = Motor Energized5 = Not Motor EnergizedUser UI Edit Lock S611 Lock S611 User interface module. (Prohibits changing S611 settings from UI)0 = unlocked1 = lockedComm loss Timeout in milli-seconds S611 Length of comloss before fault. (in .001 sec: 1–65000)Comm loss behavior S611 1 = Fault2 = Hold Last State3 = StopS611 ComLoss Enable S611 0 = disable fault1 = enable faultTable 19. S611 Soft Starter Configuration File, continuedParameter Name Location Notes PreviousNext |