Emergency On Call Service: Local representative (Eaton.eu/aftersales) or +49 (0) 180 5 223822 (de, en) 1/7Instruction LeafletMontageanweisungNotice d’installationInstrucciones de montajeIstruzioni per il montaggio安安装说明装说明Инструкция по монтажу05/18 IL01502082ZCI-K…-NAInstallation of conduits and grounding of equipment enclosures.These enclosures are intended for wall mounting only!Table: Technical data conduitSelect the size and location of conduits on theenclosure and provide conduit holes according toInstructions shown in table.Connect conduits to the enclosures according tothe instructions shown in figures 1.For grounding of equipment, install the groundingconductor in accordance with the requirements ofthe National Electric Code (N.E.C. – USA) orCanadian Electric Code (C.E.C. – Canada).Figure 1Connection of metallic and non-metallic conduitsMaximum permissible size ofconduit entryCI-K2X…-NA2 x ½“ ConduitCI-K3X…-NA2 x ¾“ ConduitCI-K4X…-NA2 x 1“, 1 x ½“ ConduitCI-K5X…-NA2 x 1½“, 1 x ½“ Conduita Connector hubb Use trade size conduit fittingsc Grounding conductord Equipment grounding terminale LocknutConduit trade size inches ½ ¾ 1 1 – ¼ 1 – ½Hole diameter inches 7/8 1 – 11/8 1 – 13/8 1 – ¾ 2mm 22 28 35 44 50Electric current! Danger to life!Only skilled or instructed persons may carry out thefollowing operations.en1 2 3ˍ CAUTIONEmpty enclosures and enclosures used withswitches for the North American markethave no knock-outs in the end walls of theenclosure. Conduit entries must be drilled tosuit as shown. The metric size conduitentries which appear in product dedicatedIL… Instruction Leaflet supplied withenclosed switches do not apply toNorth American switch enclosures.enaedcbˍ CAUTIONFirst secure the connector hub onto the conduit.Then secure conduit with connector hub into theenclosure hole, using the locknut for fixing.Bonding and grounding bushings are not required.en