INSTALLATION - MOUNTING1. Mark and drill desired location on mounting surface of the wall. Mountingbrackets will come pre-installed. Luminaire is provided with three ¾” NPTconduit entries and two plugs shipped with the luminaire, but not installed(Figure 1). Plug the conduit entries not being used. To prevent galling and toensure water tightness, lubricate conduit plugs with Eaton’s Crouse-Hinds seriesHTL lubricant before installing, and secure wrench-tight with at least five (5) fullthreads engaged (42-52 ft.-lb. for 3/4” plugs).2. Secure Wall Pack with mounting brackets to surface using 1/4” screws or lagbolts.SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCEIF 1892Champ-Pak® CPMVL LED Wall PackInstallation & maintenance informationIF 1892 • 11/19 Copyright© 2019, Eaton’s Crouse-Hinds Division Page 1APPLICATIONChamp-Pak® CPMVL are suitable for use in the following hazardous (classified)locations as defined by the National Electrical Code (NEC®)/CEC.Refer to the Wall Pack nameplate for specific classification information, maximumambient temperature suitability and corresponding operating temperature (T-code).Champ LED Wall Packs’ construction is designed for use indoors and outdoors inmarine and wet locations, where moisture, dirt, corrosion, vibration and rough usagemay be present.WARNINGTo avoid explosion,Make sure the supply voltage is the same as the luminaire voltage. Do not installwhere the marked operating temperatures exceed the ignition temperature of thehazardous atmosphere.Do not operate in ambient temperatures above those indicated on the luminairenameplate.Contact Crouse-Hinds for instructions on replacement parts.Use proper supply wiring as specified on the luminaire nameplate. All surfacesmust be clean.Before opening, electrical power to the luminaire must be turned off. Do not openwhen an explosive atmosphere is present. Keep tightly closed when in operation.To reduce the risk of ignition due to electrostatic discharge, avoid contact with theluminaire while explosive atmosphere is present. Clean only with damp cloth.!Figure 1CPMVL:NEC/CEC• Class I, Division 2, Groups A, B, C, D• Class II, Division 2 Groups F, G• Marine and Wet Locations, Type 4X, IP66UL standards• UL 844, UL1598, UL1598A, UL8750, UL50ECSA standard• cUL Listed to CSA standard C22.2 No. 250.0, CSA C22.2, No. 250.13• cUL Listed to CSA standard C22.2 No. 137 CSA 22.2 No. 25Input voltage• 120-277 VAC, 50/60 Hz• 125, 250 VDC• 347-480 VAC, 50/60 HzWARNINGTo avoid electric shock,Be certain electrical power is OFF before and during installation and maintenance.Luminaire must be supplied by a wiring system with an equipment groundingconductor.To avoid burning hands,Make sure lens and housing are cool when performing maintenance.!Mounting bracketSide conduit entryHex screws to fixmounting brackets toBack conduit entryMounting bracketSide conduit entryHex screws to fixmounting brackets to