63 Amended: April 22EMEA Fire Technical Support: DF6000/CF3000 Applications GuideFrom Jun17 a new device which also replies as a repeater has been introduced to providecompliance to this regulation.The BS 7273 interface is programmed in the same format as all previous repeaters. Right click thedevice icon and choose ‘Edit repeater’ from the drop box highlight ‘BS7273 interface’.Fig 60Two output stages are provided on this device with up to 5 rules each. Each rule, if selected forBS7273 specific, See Fig 60, will have 3 condition sources, Fire , Fault and Disablement by default.Trigger sources by Zone, device or global can then be selected. You can build your own rules ifrequired.The BS7273 device has a loop in and out connection but is powered from an external 24v PSU.If the PSU has volt free contacts for Mains and Battery Faults then the BS7273 device has 2 inputterminals with 6K8 EOL capable of monitoring the volt free contacts.NOTE These Devices can not be used on CF2000Touch Screen RepeaterThe Touch screen repeater is ONLY networkable but allows the user much more control such asdisabling devices across the network. This panel also has a programmable input and Fire and Faultrelays.