Core Power Solutions (DV2-C16 Models)92 Copyright © 2008-2009 Eaton Corporation. All Rights Reserved.IPN 997-00012-71B July 2009Connection to SystemUse RJ45 cable(s) to connect from connector XU1 on the CS04-A11 to current sense input XH6on the I/O board. Up to three current sensors can be connected to XH6. To connect more than three currentsensors use additional SiteSure-3G I/O modules. See details in the SiteSure-3G Installation andOperation Guide (refer to Related Information on page i).SC200 ConfigurationFor full configuration details refer to the SC200 Operation Handbook and/or SiteSure-3GInstallation and Operation Guide (see Related Information on page i).The following configuration is required:1 Connect to the SC200 using DCTools/Web. Refer to the SC200 Operation Handbook for communications options and configuration.2 Configure the current sense input(s).The current sense input(s) must be Enabled and configured. Refer to Enable and ConfigureI/O in the SiteSure-3G Installation and Operation Guide and the following notes:Function If the CS04-A11 current sensor is used for current monitoring which isseparate from total system load or battery current monitoring, then setFunction to User Defined.If Function is set to Battery Current or Load Current then the SC200 willadd the current measured by the CS04-A11 current sensor to thecurrent measured by other current sensors with the same Functionvalue. If the current sensors are measuring the same (or part of thesame) current the SC200 will then calculate an incorrect value for thesystem's total battery or load current.Gain Set to 10,000.Offset Set to 0.3 Calibrate the sensor.For exact calculation of Gain and Offset values for an individual current sensor refer toGain and Offset Calculation in the SiteSure-3G Installation and Operation Guide.