1. Brief introduction--4--1.4 Product specification and performanceGeneral specificationModel 10000HXL31 15000HXL31 20000HXL31Power Rating 10KVA/7KW 15KVA/10.5KW 20KVA/14KWVoltage range 322-461V~Phase Three PhaseFrequency 50/60Hz 50/60Hz 50/60HzVoltage 380-415V~RatedInput Current 51A max. 75A max. 96A max.Voltage 240VDC 240VDC 240VDCBattery Current 40A max. 60A max. 80A max.Voltage 220/230/240V~RatedOutput Current 45A max. 68A max. 91A max.Dimension (WxDxH) mm 260x570x717 260x570x717 260x570x717Weight (kg) 39 55 55Electrical performanceInputmodel Voltage Frequency Power Factor10000/15000/20000 380-415VAC 50/60Hz >0.95(Fullload)OutputVoltageRegulationPowerFactorFrequencytolerance. Distortion Overload capacity Currentcrest ratio±1% 0.7 lagSynchronized50/60HZ in Linemode (AC mode)±0.1% of normalfrequency inBattery modeTHD<2%Full load(LinearLoad)105%-130% load transfers tobypass mode after 10minutes>130% load transfers tobypass mode after 1 secondand shutdown the output after1 minute3:1maximumOperating environmentTemperature Humidity Altitude Storage temperature0°C-40°C <95% <1000m 0°C--40°Note: if the UPS is installed or used in a place where the altitude is above 1000m, theoutput power must be derated in use, please refer to the following :Altitude(M) 1000 1500 2000 2500 3000 3500 4000 4500 5000Derating power 100% 95% 91% 86% 82% 78% 74% 70% 67%WARNING: This is a product for commercial and industrial application in the secondenvironment installation restrictions or additional measures may be needed to preventdisturbances.PDF created with pdfFactory Pro trial version www.pdffactory.com