- 2 -1. Extension I/O interface 8. RUN indicator2. Address setup switch 9. ALARM indicator3. Function setup switch 10. DeviceNet connector4. RUN/STOP switch 11. DIN rail slot5. POWER indicator 12. DIN rail clip6. MS (Module Status) indicator 13. RS485 communication port7. NS (Network Status) indicator Switch Definition: RUN/STOPStatus ExplanationS TOPR UNRUN STOP Stop reading/writing data to the extension modulesSTOP RUN 1. Re-detects the extension modules2. Reading/writing data to the extension modules DeviceNet PortThe DeviceNet removable terminal block is included with the ELC-CADNETPIN Signal Color Definition123451 V- Black 0VDC2 CAN_L Blue Signal-3 SHIELD - Shielded cable4 CAN_H White Signal+5 V+ Red 24VDC Address Setup SwitchSettings Description9164 500913278256437800 ~ 63 Valid DeviceNet node address64 ~ 99 Invalid DeviceNet node addressThe address setup switches x100 and x101 set up the node address on the DeviceNetnetwork in decimal format. Valid range: 00 ~ 63Example: If you need to set the node address of the ELC-CADNET to 26, simply turnswitch x101 to 2 and switch of x100 to 6. Note:1. Please set up the node address when the power is off. The switches are only read atpower up.2. When ELC-CADNET is operating, changing the setting of the node address will notchange the address until power is cycled. Function Setup SwitchThe function setup switches are for1. Communication loss action2. Setting the baud rates of DeviceNet network (DR0 ~ DR1)