- 2 - SpecificationsItem SpecificationControl method Stored program, cyclic scan systemI/O processing method Batch processing method (when ENDinstruction is executed)Execution speed LD instructions – 0.54s, MOV instructions –3.4sProgram language Instruction List + Ladder + SFCProgram capacity 15872 stepsX External inputs X0~X377, octal number system,256 points max.Y External outputs Y0~Y377, octal number system,256 points max.Total480+32I/O(*4)GeneralM0~M511, 512 points (*1)M768~M999, 232 points (*1)M2000~M2047, 48 points (*1)Latched M512~M767, 256 points (*2)M2048~M4095, 2048 points (*2)M AuxiliaryrelaySpecial M1000~M1999, 1000 points,some are latchedTotal4096 pointsT0~T126, 127 points (*1)T128~T183, 56 points (*1)T184~T199 for Subroutines, 16points (*1)100ms(M1028=ON,T64~T126: 10ms) T250~T255(accumulative), 6points (*1)T200~T239, 40 points (*1)10ms(M1038=ON,T200~T245: 1ms)T240~T245(accumulative), 6points (*1)T Timer1msT127, 1 points, (*1)T246~T249(accumulative), 4points (*1)Total256 pointsC0~C111, 112 points (*1)C128~C199, 72 points (*1)16-bit count upC112~C127, 16 points (*2)C200~C223, 24 points (*1)32-bit count up/down C224~C232, 9 points (*2)Total233 pointsC235~C242, 1 phase 1 input, 8points (*2)Software C233~C234, 2 phase 2 input, 2points (*2)C243~C244, 1 phase 1 input, 2points (*2)C245~C250, 1 phase 2 input, 6points (*2)C Counter32-bithigh-speedcountup/down HardwareC251~C254 2 phase 2 input, 4points (*2)Total22 pointsInitial step point S0~S9, 10 points (*2)Zero point return S10~S19, 10 points (use withIST instruction) (*2)Latched S20~S127, 108 points (*2)General S128~S911, 784 points (*1)BitcontactsS SteppointAlarm S912~S1023, 112 points (*2)Total 1024points