- 4 - Electrical SpecificationsModelItem ELC2-PC12NNDR ELC2-PC12NNDTPower supply voltage24 Vdc (-15 to 20%)(with reverse polarity protection on the DC input power)ELC-PS01: input 100 to 240 Vac, output 24 Vdc/1A ELC-PS02: input100 to 240Vac, output 24Vdc/2AConnector European standard removable terminal block (Pin pitch: 3.5mm)Operation Maximum power loss time is 10ms or less.Inrush current Max. 7.5 A@24 Vdc, I 2t = 0.25 A2SFuse capacity 2.5 A/30 Vdc, PolyswitchPower consumption 1.8 W 1.5 WPower protection With reverse polarity protection on the DC input powerInsulation resistance > 5 MΩ (all I/O point-to-ground: 500 Vdc)Noise immunityESD (IEC 61131-2, IEC 61000-4-2): 8kV Air DischargeEFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,Analog & Communication I/O: 1kVRS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/mGroundingThe diameter of grounding wire cannot be smaller than the wirediameter of terminals L and N (All ELC2 controllers should begrounded directly to the ground pole).Operation / storage Operation: 0 to 55°C (temp.), 5 to 95% (humidity), Pollution degree 2Storage: -25 to 70°C (temp.), 5 to 95% (humidity)Agency approvalsUL508European community EMC Directive 89/336/EEC and Low VoltageDirective 73/23/EECVibration / shockresistanceInternational standards: IEC61131-2, IEC 68-2-6 (TESTFc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)Weight (g) 140g 131gInput PointsSpec.Items 24 Vdc (-15 to 20%) single common port inputInput No. X0 to X2 X3 to X7Input type DC (SINK or SOURCE)Input current (±10%) 24 Vdc, 5 mAInput impedance 4.7 kΩMax. frequency 100 kHz 10 kHzOff On > 15 VdcActionlevel On Off < 5 VdcOff On < 2.5 μs < 20 μsResponsetime On Off < 5 μs < 50 μsFilter time Adjustable within 0 ~ 20ms by D1020 (Default: 10ms)Output PointsSpec.Items Relay TransistorOutput No. Y0 to Y3 Y0, Y2 Y1, Y3Max. frequency 1 Hz 100 kHz 10 kHzWorking voltage 250 ac, < 30 Vdc 5 to 30 Vdc #1Resistive 1.5 A/1 point (5 A/COM) 0.5 A/1 point (2 A/COM)Inductive #2 15 W (30 Vdc)Max. loadLamp 20 WDC/100 WAC 2.5 W (30 Vdc)Off On 2 μs #3 20 μs #3Responsetime On Off Approx. 10 ms 3 μs #3 30 μs #3#1: UP, ZP must work with external auxiliary power supply 24 Vdc (-15 to +20%), ratedconsumption approx. 1mA/point.#2: Life curvesContactcurrent(A)0.50.1 0.2500.3 0.7 1 22003005001001,0002,0003,000Operation(X10 )3120 VAC, resistive30 VDC, inductive (t=7ms)240 VAC, inductive (cos 0.4)ψ=120 VAC, inductive (cos =0.4)ψ30 VDC,inductive(t=40ms)[ Figure 2 ]