3 Commissioning3.3 Error acknowledgmentElectronic motor starter EMS-...-SWD 12/18 MN034002ZU-DE/EN www.eaton.com 633. AutomaticallyIf output bit 0.3 (RES_AUT) is permanently set, the electronic motor starterwill automatically acknowledge faults after the bi-metal relay is actuated andthe unit goes through a subsequent cool-down period (20 minutes). DANGERAutomatic restarting may result in bodily injury and/or propertydamage.There is a danger of automatic restarts occurring when the“automatic reset” operating mode (output bit 0.3 (RES_AUT)permanently set to 1) is being used.The unit will restart automatically after the cool-down period of20 minutes elapses.