Page 26 - 34007724EN/ADOFF ONUPS SET UPEXIT ENTOFF ON3. Operation3.1 Initial start upCheck that the manual bypass switch 7 is on Normal position.Set the normal AC source circuit-breaker 9 to the "I" position.Set the battery circuit breaker 12 to the "I" position.The load is powered via the bypass AC source, but not protected bythe UPS.Batteries are recharging, an eight-hour recharge period is necessaryto get full backup time.LED 15 is ON.PRESS ONTO STARTUPSIf specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software forWindows included in the EATON Solution-Pac power management suite CD-ROM.Press "scroll up"z 19 and "scroll down" 20 function buttonstogether for more than 3 seconds.Press the function buttonz 20 placed under the ENT word toenter the set up mode and follow the LCD messages using thebuttons now defined as select keys.Local settingsPersonnalisation de la sortie(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity(with potential 10 ms break).Accessing personalisation with front panel buttonsUPS personalisation1519 20Function Factory setting OptionsLanguage English French, Spanish, German, Italian.Date / time format International format(DD-MM-YYYY/HH:MM)US format (MM-DD-YYYY/HH:MM AM/PM).Date / time change Time in France MM-DD-YYYY/HH:MM adjustable.Audible alarm Quick beeps Slow beeps.Function Factory setting Options CommentsOutput voltage 230 Volts AC 200/208/220/240/250Frequency converter Disabled Enabled Bypass AC source disabled.Output frequency Auto ranging 50/60 Hz User selectable underfrequency converter mode.Eco mode Disabled Enabled See glossary.Hot standby Disabled Enabled N+1 redundancy(See section 2.5 "Hotstandby").Operating mode Industrial I/T Network (*)Transfer on Bypass ACsourceIf the Bypass AC sourceis out of tolerancesIf the Bypass AC sourceis inside tolerances (*)Break time 10 ms 10 to 200 ms(by steps of 10 ms) Break time calibration duringload transfer on Bypass ACsource out of tolerances.Overload level 102 % 50/70 %