EATON Diesel Plus O & M Manual IM05805019K-002Diesel Engine Fire Pump Controller Effective April 2015EATON INDUSTRIES CANADA COMPANY www.chfire.com 53.1.4 AC Input Fuse ProtectionThe AC Supply is protected by a 6 amp fuse which will blow incase of a breakdown of the charger. This fuse will not blow as aresult of overloading of the charger since the electronics willshutdown the charger in this event before the fuse blows. If thisfuse is blown the charger must be replaced.3.1.5 Battery Charger DisplayThe Diesel Plus chargers history will display Charging Voltageand Amperage as well as error messages. The following will berecorded according to the conditions that exist.“NO BATTERY” is displayed if no battery is attached to thecharger.“BATTERY ERROR” is displayed if a battery is connected to thecharger but the voltage is not within the minimum andmaximum thresholds for the selected battery type.“ERROR, RECOVERING” is displayed if the maximum batterycharger output voltage (31.4V) has been exceeded.3.1.6 Charger Setup: Lead Acid / NiCadDIP switches on the charger can be used to select a number ofoptions including battery type and voltage as well as ForcedCharging. Options currently supported for the charger include12 or 24 Volt Lead Acid and NiCad Batteries.Lead AcidTo select 12 Volt battery charge cycle with Lead Acid batteriesset all DIP switches to the OFF position.To select 24 Volt battery charger cycle with Lead Acid batteries,set DIP switch 3 to the ON position and all other DIP switches tothe OFF position.NiCadTo select 12 Volt battery charger with NiCad batteries, set DIPswitch 6 to the ON position and all other DIP switches to theOFF position.To select 24 Volt battery charger cycle with NiCad batteries, setDIP switches 3 and 6 to the ON position and all other DIPswitches to the OFF position.3.1.7 Forced ChargingThere is provision for the battery chargers to provide a forcedcharge to the batteries. The Forced Charge function will onlyactivate immediately after applying power to the charger withDIP Switch 8 in the ON position and a battery connected.When the charger is in the forced charge mode, it will attemptto recover a battery by delivering 10 amps. If the battery doesnot reach the minimum battery voltage (8 volts for a 12 voltsystem; 16 volts for a 24 volt system) within 5 minutes, therecovery attempt will terminate. Once the battery reaches it’sminimum battery voltage, the normal charge sequence willcommence.Forced charging will only occur once per battery charger powercycle.NOTEWhen installing a replacement charger in controllers prior to the DieselPlus – DIP Switch number 5 must be switched to the ON position.3.1.8 SpecificationsVoltage Input:120 - 240VAC - Auto detectVoltage Output: 12-24VDC-DIP switch selectableHertz: Operates on 50 / 60Hz3.2 Front Operator PanelThe front operator panel, is normally accessible from theoutside of the door. The front panel provides a means to:• Alert the user to specific conditions• Program the controller• Set and monitor the operating parameters• Perform a manual start of the controller.1ONOFF2 3 4 5 6 7 812 Volt - Lead Acid12 Volt - Lead AcidONOFF1ONOFF234 5 6 7 824 Volt - Lead Acid24 Volt - Lead AcidONOFF1ONOFF2 3 4 567 812 Volt - NiCad12 Volt - NiCadONOFF1ONOFF234 567 824 Volt - NiCad24 Volt - NiCadONOFF1 11 1ON ONON ONOFF OFFOFF OFF2 22 23 33 34 44 45 55 566667 77 7812 Volt - Lead Acid 12 Volt - NiCad24 Volt - Lead Acid 24 Volt - NiCad88824 Volt - NiCadONOFF12 Volt - NiCadONOFF12 Volt - Lead AcidONOFF24 Volt - Lead AcidONOFF |
Related manuals for Eaton FDF120
This manual is suitable for:
manualsdatabase
Your AI-powered manual search engine