Eaton IQ 250 Quick Start Manual
Also see for IQ 250: User & installation manualUser & installation manual
IQ 250/260 Transducerwww.eaton.com IB02601005E Q-2Program the IQ 250/260T Using RS-485Q Communication WiringThe IQ 250/260T’s RS-485 port uses standard 2-wire, Half Duplex Architecture.Connect to Master and Slave devices as shown (+ to +, - to -).Q Factory Initial Default SettingsWhen the IQ 250/260T is powered up, for 10 seconds you can connect to the meterusing the Factory Default Settings (even if the Device Profile has been changed). After10 seconds the Device Profile reverts to the actual Device Profile in use. This is oneway you can always connect to the meter. The Factory Initial Default Settings are:Device Address: 1Baud Rate: 9600Protocol: Modbus RTUQ Connection Steps1. Open IQ 250/260 Configuration Software.2. Click Connect on the Tool Bar. The Connect screen opens. Make sure yoursettings match those shown on the right.3. Click Connect. The Device Status screen confirms the connection.4. Click OK. The main screen opens.Q Configuration Steps5. Click the Profile button on the Tool Bar. The Device Profile screenopens, showing the CT, PT Ratios and System Hookup (Scaling)fields.6. Configure Scaling settings based on your application.7. Click Communications and select settings based on your application.Q Scaling (CT, PT Ratios and System Wiring)CT Numerator, Denominator, Multiplier, CT Fullscale (Calculated automatically)PT Numerator, Denominator, Multiplier, PT Fullscale (Calculated automatically)System Wiring: Use pull-down menu to select.Number of Phases: One, Two or ThreeNOTE: Voltage Full Scale = PT Numerator x PT MultiplierCurrent Full Scale = CT Numerator x CT MultiplierIMPORTANT! Specify Primary and Secondary Voltage in Full Scale (NOTRatios).Example CT Settings:200/5 Amps: Set the Ct-n value for 200, Ct-S value for 1.800/5 Amps: Set the Ct-n value for 800, Ct-S value for 1.2,000/5 Amps: Set the Ct-n value for 2000, Ct-S value for 1.10,000/5 Amps: Set the Ct-n value for 1000, Ct-S value for 10.Example PT Settings:14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10.138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100.345,000/115 Volts: Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100.345,000/69 Volts Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000.Q Communications SettingsCOM2 (RS-485):Address (1-247)Protocol (Modbus RTU, ASCII or DNP)Baud Rate (9600 to 57600)Response Delay (0-750 msec)Q Update Device8. When settings are complete, click the Update Device button to send a new profile to the IQ 250/260T.9. Click Exit or click other tabs to update additional screens.10. Use IQ 250/260 Configuration Software to communicate with the device and perform requiredtasks.NOTE: For further details and additional programming screens, see the IQ 250/260 Manual on the enclosed CD. |
Related manuals for Eaton IQ 250
manualsdatabase
Your AI-powered manual search engine