Conversion kit LED8the light fitting).• All metal work within an earthed fittingMUST be securely earthed, includingreflectors and louvers.• Keep cables as short as possible.• Mains wiring must exit fitting from nearestentry/exit point.• Keep mains wiring away from the LED lampcables for better EMC performance.• In SELV conversion applications keepmains wiring separated from the battery,LED lamp and indicating LED wiring or usespecial (double insulated) wiring.TERMINAL CONNECTIONS• Connect the neutral to ‘N’ terminal of theconverter and to the mains LED driver neutralinput terminal. Connect the unswitchedlive to terminal ‘L’ and the switched live interminal ‘L1 In’ on the converter. Connectconverter’s ‘L1 OUT’ terminal to the mainsLED driver live input terminal.• Connect the yellow/white or red/brown LEDwire to the terminal marked ‘LED Y’/'LEDW' or 'LED R'/'LED B' respectively.• Connect the two cables for the telelcommandsignal on the '-A'/'+B' terminal blocks(polarity sensitive connection). Connect thetwo cables from CGL+ or Dali bus on the'CGL+' or 'Dali' terminal blocks respectively(polarity free connection).• Ensure the light fitting is securely earthedNote: Make sure that the terminals on the modulecannot be touched when changing the lamp orstarter by shrouding them with earthed metal orthermoplastic insulation.TESTING THE CONVERSIONElectrical TestsEarth Continuity: Earth resistance between earthterminal and all metal parts must be less than 0,5ohms at 10 Amps.Electrical Strength: Ensure that there is nobreakdown when use 1500V ac (50/60Hz) testvoltage between the Neutral and Live bondedtogether and the Earth terminal.Testing an Installed Fitting:• Connect mains voltage to the unswitchedlive supply and ensure that the LED is lit.• Connect mains voltage to the switched andunswitched live supplies and check that thelamp lights correctly.• Apply mains supply to the unswitched livefor a minimum of 10 min. Disconnect thesupply and check that the emergency lamplights.• It is recommended that a full duration test iscarried out by applying the mains supply for