MEMSHIELD 4 INSTALLATION INSTRUCTIONS FOR 400A PANELBOARDS/ PAN ASSEMBLIESEM4PB840, EM4PB1440, EM4PB1840EM4PBP840, EM4PBP1440, EM4PBP1840Instruction Leaflet LT1222 (02/19)400A Incoming MCCB EM4PBK404Removefor accessIncoming Modules3 Pole & Neutral - Bottom EntryForm 4 Type 6 Group MountedSecureallshields4 Pole - Bottom EntryForm 4 Type 6 Group MountedSecureallshields400A Incoming Direct Cable EM4PBK404L4 Pole - Bottom EntryForm 4 Type 6Secureallshields30NmRemovefor accessFitMountPanelboard’s are supplied as Bottom Entry and Form 4 Type 6 Group Mounted without modificationGeneral Note: When fixing M5 thread formingscrews tightening torque is 3.8 NmFit shieldRemoveincomingmount.400A Incoming Neutral EM4PBNK40N L1 L2 L330NmClick cover shield in toincoming cover apertureN L1 L2 L3IncomingmountFit neutralBottomEntryIMPORTANT NOTES1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician inaccordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring RegulationsBS7671), Construction (Design and Management) Regulations, HSG150 – Health and Safety in Construction, Statutory requirementsand any Specific instruction issued by the Company.2. After completing the installation and testing of this product it is essential that this leaflet is drawn to the attention of the personresponsible for its future operation and maintenance, and is at all times available for ready reference.3. The notes assume throughout that the product is disconnected from the supply. It is essential that this is done before any work iscarried out.4. These Panelboards are only designed for use with EATON MCCBs. Failure to comply will result in invalid warranty and certification.31Nm31NmFitInterphaseshields