Instruction LeafletMontageanweisungNotice d’installationInstrucciones de montajeIstruzioni per il montaggioИнструкция по монтажуMontagehandleidingMontagevejledningΟδηγίες εγκατάστασηςInstruções de montagemMonteringsanvisningAsennusohjeNávod k montážiPaigaldusjuhendSzerelési utasításMontāžas instrukcijaMontavimo instrukcijaInstrukcja montażuNavodila za montažoNávod na montážМонтажни инструкцииInstrucţiuni de montajUpute za montažuKullanma TalimatıИнструкција за монтажуIntruksjonsbladМонтажна інструкціяت ة ا INSTRUCTIONS FOR INSTALLATION Shunt Trip Release Z-LHASA1. Function and Description:The shunt trip release type is a remote release based on the working current principle. The de-vice for modular installation has been designed for installation on DIN support bars according to EN 50022. It is1,5 MU (=27 mm) wide, has an optical switching position indicator (red/green) and can be mounted subsequentlyon the left hand side onto any PLHT, miniature circuit breaker of up to 6 module units. Remote tripping is possiblewithin a wide voltage range. An auxiliary switch Z-LHK which can be connected additionally permits transmissionof a message that switchoff has occurred.The sequence of installation as shown in the diagram must be observed, i.e. the shunt trip release must alwaysbe installed to the left of the PLHT and the auxiliary switch Z-LHK on the right side.When applying a voltage within the permitted range, the shunt trip release responds virtually without delay andcauses internal tripping of the PLHT mounted next to it. At the same time, it cuts the power supply to its own tripcoil and thus prevents thermal overload of the triipping device in case of continuous tripping commands. Conse-quently, excessive length of the tripping pulse does not cause damage to the device. However, a minimum pulselength is required for reliable functioning. The switching toggles of the Z-LHASA and PLHT are coupled mechani-cally in such a way that when the PLHT is activated the toggle of the Z-LHASA is moved simultaneously. In casethe PLHT is switched off manually, the Z-LHASA trips mechanically even if no control voltage is present. In caseof electric tripping of the PLHT, the Z-LHASA is also activated internally by mechanical means and goes to theOFF-position. If an external obstacle prevents the ASA switching toggle from moving to the OFF-position, the de-vice may still trip internally like any PLHT independently of the toggle position.2. Technical Data:AC range ~ 24V 230VResponding limit (V) 8 70Operating voltage range (V) 12 - 60 110 - 415Max. current consumption at the moment of switching on (A) 18 (at 24V) 2 (at 230V)Duration of current flow at max. current consumption (ms) 4,5 4,5DC range =Responding limit (V) 11 90Operating voltage range (V) 12 - 60 110 - 230Max. current consumption at the moment of switching on (A) 18 (at 24V) 2 (at 230V)Duration of current flow at max. current consumption (ms) 2 4Minimum pulse duration (ms) 15 10Internal resistance (Ohm) 2,0 130Duty (%) 100Tripping time (ms) < 20Peak withstand voltage (1,2/50ms) (kV) 2Service live operating cycles > 4000Upper/lower terminals lift / liftConductor cross section mm² 2,5 - 50GB1