Programming9402/09 AWB2723-1612enCompatibility The gateway stores the data of the devices actuallyconnected when the configuration button is pressed (=stored gateway target configuration).Each time the gateway starts it is checked whether thisconfiguration has been changed. If this is the case, the datainterchange between the gateway and the SmartWireDarwin slaves is not started (missing slaves are not includedin this comparison; decisive is that the slaves found areidentical).A project configuration is specified via the programmingsystem by selecting the SmartWire-Darwin slave (= plannedtarget configuration). This is downloaded automatically tothe gateway by the Moeller programming system duringtransfer of the program to the controller.Description SmartWire Darwinstatus LEDData interchangebetween the gateway andSmartWire Darwin slavesThe current actual configuration complieswith the gateway target configuration.Green continuous light yesA necessary SWD slave is missing or thegateway target configuration does notcomply with the actual configurationFlashing (red) NoSlave addressing is active (after powerOn or the download of a plannedconfiguration with empty modules).Flashing (green) NoShort circuit on the 15 V power supply orno SmartWire Darwin slave is connected.Red continuous light No