PXG 900 User's Guide - Firmware Version 4.3 - 1/9/2017111.2.3.4.5.6.7.8.9.1.2.3.4.5.6.7.8.9.10.11.Initial SetupThe PXG helps you when adding devices, guiding you through the initial setup steps:To add either a Modbus RTUor INCOM device:Choose Edit.Choose Add Device under the appropriate port.In the sidebar, select the device type under Family.Select the Model Series.Select the device Model.Enter a meaningful name for the device.Enter the device address: 1-247 decimal for Modbus, 1-FFE hexadecimal for INCOM. If you enter an addressthat's already in use, the box outline will turn red and you won't be able to save the device configuration untilyou select a unique address.If Enable Waveforms is available, decide whether you wish to have the PXG capture these.Choose Save Device Configuration.The following examples assume that the devices are on the appropriate networks and that the ports are properlyconfigured.Example 1: Adding An IQ 250 MeterConnect the IQ 250 Meter to either COM1 or COM2.Choose the Network tab.Choose Edit.Choose Add Device under the appropriate COM port column.Select Meters under Family.Select IQ 200 Series under Model Series.Select IQ250 under Model.Enter a name, such as "IQ250_1" under Name.Set the Serial Address (1-247 decimal) to match the address you set on the meter.Choose Save Device Configuration.Choose Edit.