AP040092EN _DE1 Quick-Start-Guide www.eaton.eu Page 23PNU SWDAddressAccessRUNDesignation Range Default Description2 = 38.4 kBit/s3 = 57.6 kBit/s4 = 115.2 kBit/sP-36 362.0 Y r/w Modbus RTU0 COM Timeout 0…8 0Modbus RTU0 COM TimeoutTime between a communication loss and the resulting action.Setting “0” disables the action after communications trip.t: indicates the VSS will trip if time exceeded.r: indicates the VSS will ramp to stop if time exceeded.0 = no action1 = t 30 ms2 = t 100 ms3 = t 1000 ms4 = t 3000 ms5 = r 30 ms6 = r 100 ms7 = r 1000 ms8 = r 3000 msP-37 976.0 - r/w Parameter Set 0/1 0 Restores factory parameter settings.1 = Restore (This is reset to 0 by the VSS).P-38 320.1 Y w Password Level2 0…9999 101 Defines the password which is used to get access to extendedparameter set (Level 2). Access via P-14.P-39 625.0 Y r/w Parameter Lock 0/1 0Determines whether to lock the parameters0 = Unlocked. All parameters can be accessed and changed1 = Locked. Parameter values can be displayed, but cannot bechanged. If a remote keypad is connected, parameters cannot beaccessed by the remote keypad if they are locked.P-40 840.29952 Y r/w Action@Communication Loss 0 … 4 0VSS reaction after SWD master communication loss. Master com-munication loss delay time is set by P-360 = No reaction, continue work1 = Set warning, continue work2 = stop (if ramp enabled)3 = coast stop4 = TripP-41 927.0 Y r/w Parameter Access 0/1 0Parameter Access0 = All parameters can be changed by any source.1 = All parameters locked; can only be changed by the SWD device.Display ValuesP00-01 560.0 Y r Analog Input1 0.0% …100% - Level of the signal applied to analog input 1 after scaling and offsetshave been applied.P00-03 1.0 Y r Frequency Reference 0.0…300 Hz - Value of the VSS internal digital reference (used for keypad)P00-04 550.0 –550.n Y r DI1 Status 0000b-1111b - Status of the digital inputs starting on the left hand side withdigital input 1 etc.P00-05 504.0 Y r Motor Current 0 … 150 % Ie - Instantaneous output currentP00-06 502.0 Y r Output Frequency 0.0 … 300.0Hz - Instantaneous output frequencyP00-07 501.0 Y r Motor Voltage 0…480 VRMS - Instantaneous output voltageP00-08 501.1 Y r DC-Link Voltage V - Instantaneous DC Link VoltageP00-09 822.0 Y r Heatsink Temperature oC - Instantaneous Heatsink TemperatureP00-10 821.0 Y r t-RunTotal operating time of the VSS since the date of manufacture inhours, minutes and seconds. Pressing the UP key on the VSS keypadwill change the display from "hours" to "minutes and seconds".P00-11 Y r RunSincePowerOnTotal operating time of the VSS since the last trip occurred or thelast power ON in hours, minutes and seconds. Pressing the UP keyon the VSS keypad will change the display from "hours" to "minutesand seconds"P00-12 821.5 Y r RunSinceLastTripTotal operating time of the VSS since the last trip occurred in hours,minutes and seconds. Pressing the UP key on the VSS keypad willchange the display from "hours" to "minutes and seconds"P00-13 821.3 Y r t-HoursRunEnableTotal operating time of the VSS since the last VSS ENABLE signal wasapplied. Pressing the UP key on the VSS keypad will change thedisplay from "hours" to "minutes and seconds"P00-14 390.1 Y r Actual Switching Frequency Switching frequency set with P-29 is displayed. The value may beless than the one set with P-29 when the thermal management of