INSTALLATIONEATON Powerware® 9125 Two-in-One PDM (5000/6000 VA) User’s Guide S 164201519 Rev Ewww.powerware.com29Table 3. Plug-Receptacle PDM Input/Output Voltage SettingsPPDM L6-30 and PPDM L6-20 Models Output VoltageInput Voltage(from UPS) 208V Switch Position Default 240V Switch Position(from UPS)L6-30R or L6-20R 5-15R L6-30R or L6-20R 5-15R208 208 120 208 104220 220 126 220 110230 230 131 230 115240 240 136 240 120Input Voltage PPDM L5-30 Models Output VoltageInput Voltage(from UPS) 208V Switch Position Default 240V Switch Position208 120 104220 126 110230 131 115240 136 120PPDM L14-30 Models Output VoltageInput Voltage(from UPS) 208V Switch Position Default 240V Switch Position(from UPS)L14-30R 5-15R L14-30R 5-15R208 240 120 208 104220 252 126 220 110230 262 131 230 115240 272 136 240 120PPDM L6-30&L14-30 Models Output VoltageInput Voltage(from UPS) 208V Switch Position Default 240V Switch Position(from UPS)L6-30R L14-30R 5-15R L6-30R L14-30R 5-15R208 208 240 120 208 208 104220 220 252 126 220 220 110230 230 262 131 230 230 115240 240 272 136 240 240 120