POWER WIRING INSTALLATION NOTES011509D164201604-5 3 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:INSTALLATION INFORMATIONEATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual 164201604 Rev D www.powerware.comA-14Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for the Powerware 9390-160/160Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pFloadkVAkW160144160144160144160144160144Input and Bypass InputOutputVOLTSVOLTS208/220208/220380380400400415415480480AC Input to UPS Rectifier(0.98 min. pF)Full Load Current plus BatteryRecharge Current(3) Phases, (1) Ground A Amps 480 275 255 250 210Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)2/0(2)2/0(2)2/0(2)1/0(2)AC Input to UPS BypassFull Load Current(3) Phases, (1) Neutral-if required,(1) Ground B Amps 444/420 243 231 223 193Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)2/0(2)2/0(2)2/0(2)1/0(2)DC Input from Battery to UPS(1) Positive, (1) NegativeCVdcAmps@(2.0V/cell)384-480403432-480403432-480403432-480403432-480403Minimum Conductor SizeNumber per PoleAWG or kcmil(each)250(2)250(2)250(2)250(2)250(2)AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1)Ground DAmps 444/420 243 231 223 193Minimum Conductor SizeNumber per PhaseAWG or kcmil(each)400(2)2/0(2)2/0(2)2/0(2)1/0(2)Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 7) - AWG or kcmil(each)1/0(2)2(2)2(2)2(2)2(2)NOTE: Callout letters A, B, C, and D map to Drawing 164201604-4, sheets 1 of 6, 2 of 6,4 of 6, 5 of 6, and 6 of 6.7. If the load requires a neutral, a bypass source neutral must be provided. If the load doesnot require a neutral and there is no neutral conductor connected at the bypass input, aneutral to ground bonding jumper must be installed. DO NOT install both a source neutraland a bonding jumper. See Table E through Table G for neutral bonding jumper wire sizes.Bonding jumper must be copper wire.C A U T I O NHIGH IMPEDANCE GROUND SOURCES - If the source of supply is a high impedance ground (IT) type, the input neutralconductor must be connected from the source of supply. If there is no output neutral connected to the UPS, theneutral‐forming transformer kit (PN 103005400) may be used instead of pulling a neutral from the source. If the load requiresa neutral then an input neutral conductor must be pulled into the UPS. In no circumstances shall a neutral to ground bondingjumper be installed in the UPS.