POWER WIRING INSTALLATION NOTES011509D164201604-5 13 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:INSTALLATION INFORMATIONEATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual 164201604 Rev D www.powerware.comA-24Table P. INPUT/OUTPUT Ratings for Powerware 9390-120/120 and 9390-160/120 Parallel SystemsConfiguration Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW120108120108120108120108120108Input and Bypass InputOutputVOLTSVOLTS208/220208/220380380400400415415480480AllAC Input from UPMFull Load Current for each Module(3) Phases, (1) Neutral-if required, (1) Ground DAmps 333/315 182 173 167 144Minimum Conductor Size for each ModuleNumber per Phase for each ModuleAWG or kcmil(each)See Table E through Table G for wiresize.1+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 333/315 182 173 167 144AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 333/315 182 173 167 144System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)1/0(1)2(1)2(1)2(1)4(1)2+0and2+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 666/630 364 346 334 288AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 666/630 364 346 334 288System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)3/0(1)1/0(1)1/0(1)1/0(1)1/0(1)3+0and3+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 999/945 546 519 501 432AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 999/945 546 519 501 432System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)1/0(2)2/0(1)2/0(1)2/0(1)2/0(1)4+0AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 1332/1260 728 692 668 576AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral-if required, (1) GroundG Amps 1332/1260 728 692 668 576System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 27)- AWG or kcmil(each)2/0(2)3/0(1)3/0(1)3/0(1)2/0(1)NOTE: Callout letters D, F, and G map to Drawing 164201604-4, sheets 4 of 6, 5 of 6,and 6 of 6.