Installing the UPS System3-6 EATON Powerware® 9390 UPS (20–80 kVA) Installation and Operation Manual S 164201603 Rev 1 www.powerware.com3.2.3 Integrated Distribution Cabinet InstallationTo install and wire an IDC, refer to the Powerware 9390 Integrated Distribution Cabinet(80 kVA) Installation and Operation Manual. After the IDC is installed and wired, return toparagraph 3.2.6 to complete the UPS cabinet wiring.3.2.4 Integrated Accessory Cabinet InstallationTo install and wire an IAC, refer to the Powerware 9390 Integrated Accessory Cabinet (IAC-Band IAC-T Configurations) Installation and Operation Manual or the Powerware 9390Integrated Accessory Cabinet (IAC-D Configuration) Installation and Operation Manual.After the IAC is installed and wired, return to paragraph 3.2.6 to complete the UPS cabinetwiring.3.2.5 UPS Sidecar WiringTo wire an UPS Sidecar, refer to the Powerware 9390 UPS Sidecar Installation andOperation Manual. After the UPS Sidecar is wired, return to paragraph 3.2.6 to completethe UPS cabinet wiring.3.2.6 Installing UPS External and Battery Power WiringNOTE The UPS cabinet is shipped with a debris shield covering the ventilation grill ontop of the unit. Do not remove the debris shield until installation is complete. However,remove the shield before operating the UPS. Once the debris shield is removed, do notplace objects on the ventilation grill.NOTE Remove the UPS cabinet top or bottom conduit landing plate to drill or punchconduit holes (see Drawing 164201603-6 on page A-32).NOTE If the load requires a neutral, a bypass source neutral must be provided. If theload does not require a neutral and there is no neutral conductor connected at thebypass input, a neutral to ground bonding jumper must be installed. DO NOT installboth a source neutral and a bonding jumper. See Table E through Table J or Table Sthrough Table V for neutral bonding jumper wire sizes. Bonding jumper must becopper wire.C A U T I O NHIGH IMPEDANCE GROUND SOURCES - If the supply source is a high impedance ground (IT)type, the input neutral conductor must be connected from the source of supply. If there is nooutput neutral connected to the UPS, the neutral-forming transformer kit (PN 103005400) maybe used instead of pulling a neutral from the source. If the load requires a neutral, then aninput neutral conductor must be pulled into the UPS. In no circumstances shall a neutral toground bonding jumper be installed in the UPS.