INS #IB505020EN 049-276 SURE-LITESInstallation Instructions for the Sure-Lites XR6C-LED Emergency LightWARNINGRisk of Fire/Electric ShockIf not qualified, consult an electrician.WARNINGRisk of Electric ShockDisconnect power at fuse or circuit breaker beforeinstalling or servicing.Important SafeguardsWHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETYPRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDINGTHE FOLLOWING.1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS2. Do not use outdoors.3. Do not use in hazardous locations, or near gas or electricheaters.4. Do not let power supply cords touch hot surfaces.5. Use caution when servicing batteries. Battery acid cancause burns to skin and eyes. If acid is spilled on skin or ineyes, flush acid with fresh water and contact a physicianimmediately.6. Do not use this equipment for other than the intended use.7. Installation is to be performed only by qualified personnel.8. Install in accordance with National Electric Code and localregulatory agency requirements.9. The use of accessory equipment not recommended by themanufacturer may cause an unsafe condition.10. Equipment should be mounted in locations and at heightswhere it will not readily be subjected to tampering byunauthorized personnel.11. SAVE THESE INSTRUCTIONSMAX MOUNTING HEIGHT: 27.6 ft.INSTALLATION1. De-energize the circuit at the junction box (J-box) wherethe emergency light is to be installed.2. Open the emergency light by inserting a screwdriver in thetwo slots on either side of the unit, then tipping the coverup off of the backplate (See Fig. 1).3. To mount to a junction box - Knock out the appropriatemounting pattern and the wire pass hole in the backplateto fit the J-box being used.4. To mount using conduit, mount the backplate to the wallin the desired location. Attach a conduit hub to whichever of the three conduit mount points on the backplate ismost convenient. (see Fig. 2) Remove the correspondingU shaped cover from the housing by wiggling it back andforth until it breaks free. (see Fig. 3)NOTE: A fourth conduit mount location is available on thebottom surface of the housing, but it can only be used withflex conduit.5. Once the backplate is secured, the housing can be held inplace during installation using the EZ Hang feature.(see Fig. 2)6. Connect the incoming wires to the fixture’s power supplywires using the wire nuts provided. Connect ground to thegreen ground wires. Connect the white wire to neutral. Ifusing 120V, connect the black wire to the hot lead. If using277V, connect the orange wire to the hot lead. Cap theunused lead (see Schematic).7. Hook the top of the housing to the top of the backplate,and swing the housing down until it snaps into place.(see Fig. 1)8. Remove the EZ key battery disconnect.9. Energize AC supply. The test button should illuminate, andLED heads will illuminate briefly when the test button ispushed.10. Adjust the heads as needed.11. If the fixture is to be powered down for an extendedperiod after initial installation, replace the EZ Key. Thiswill prevent the battery from discharging when AC poweris removed. However, it will also prevent the batteryfrom charging when AC power is restored, so it must beremoved once the unit is ready for regular operation.Figure 1Insert screwdriverin slots in bothsides while gentlylifting the housing torelease snaps andopen housing.