3Technical Data TD450157ENEffective August 2022Eluxa horns, horn strobes, & strobesEATON www.eaton.comTable 4. Specification & Ordering InformationModel Mounting Strobe Candela Red White Lettering Sync w/ DSM orWheelock Power SuppliesHorn strobesELHSRELHSWELHSR-AELHSR-NELHSW-AELHSW-ALELHSW-NELHSW-EVELHSRCELHSWCELHSWC-NWallWallWallWallWallWallWallWallCeilingCeilingCeiling15/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/150/17715/30/75/110/150/17715/30/75/110/150/177XXXXXXXXXXXFIREFIREAGENTNo LetteringAGENTALERTNo LetteringEVACUATEFIREFIRENo letteringXXXXXXXXXXXStrobesELSTRELSTWELSTR-AELSTR-ALELSTW-AELSTW-ALELSTW-NELSTR-NELSTW-EVELSTRCELSTWCELSTRC-ALELSTWC-ALELSTWC-EVWallWallWallWallWallWallWallWallWallCeilingCeilingCeilingCeilingCeiling15/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/135/18515/30/75/110/150/17715/30/75/110/150/17715/30/75/110/150/17715/30/75/110/150/17715/30/75/110/150/177XXXXXXXXXXXXXXFIREFIREAGENTALERTAGENTALERTNo LetteringNo LetteringEVACUATEFIREFIREALERTALERTEVACUATEXXXXXXXXXXXXXXHornsELHNRELHNWELHNRCELHNWCWallWallCeilingCeilingXX XXNo LetteringNo LetteringNo LetteringNo LetteringXXXXAccessoriesELSBB-RELSBB-WESB-KIT-RESB-KIT-WLSPKBB-CRLSPKBB-CWLED Backbox, wallLED Backbox, wallTrim Plate, wallTrim Plate, wallBackbox, ceilingBackbox, ceilingXXXXXXa RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). Forstrobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for24v units). For unfiltered FWR ratings, see installation instructions.b Regulated Voltage Range - VDCTable 2. Strobe ratingsEluxa Horn StrobesUL/ULC Max Current a at AnechoicHigh continuous24VDCModel Regulated VoltageRange VDC 15 30 75 110 135 150 177 185ELHSELHSC 16.0-33.016.0-33.0 0.0370.037 0.0460.046 0.0770.077 0.1090.109 0.146 0.146 0.208 0.208Table 3. Code 3 horn strobe ratingsUL/ULC Max Current a24VDCModel Regulated VoltageRange VDC 15 30 75 110 135 150 177 185ELSTELSTC 16.0-33.016.0-33.0 0.0220.022 0.0300.030 0.0600.060 0.0860.086 0.125 0.125 0.185 0.185Eluxa Horn StrobesUL/ULC Max Current a at AnechoicLow continuous24VDCModel Regulated VoltageRange VDC 15 30 75 110 135 150 177 185ELHSELHSC 16.0-33.016.0-33.0 0.0300.030 0.0390.039 0.0700.070 0.1020.102 0.139 0.139 0.201 0.201ote:N Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with CooperWheelock Inc., dba Eaton standard terms and conditions.