Menvier40/100 InstallationPage 23Figure 39 FSL Zone Wiring – Control UnitFigure 40 shows the wiring connections for FSLzones on the EXP-W10 expander. Note that theconnections are different on the expandercompared with the control unit.Zone 0Zone 1 2K2 EOLWired Expander4K7Alarm contactsTamper contacts2K2 EOL4K7Alarm contactsTamper contacts100 OhmsZ0 Z1 Z2 Z3 Z4Figure 40 FSL Zone Wiring – EXP-W10The allowed values for Alarm Contact/End of Lineresistors are: 4k7/2k2. 1k0/1k0, 2k2/2k2, or4k7/4k7.Note: Use the same pair of values for ALL FSLwired circuits on the control unit. Each wiredexpander can use a different pair of resistorvalues, but ALL circuits on an expander musthave the SAME values.Figure 41 shows The wiring connections for FSLzones on the EXP-WCC.Zone 0Zone 1 2K2 EOLWired Expander4K7Alarm contactsTamper contacts2K2 EOL4K7Alarm contactsTamper contacts100 OhmsFigure 41 FSL Zone Wiring – EXP-WCCThe allowed values for Alarm Contact/End of Lineare the same as for the EXP-W10.Figure 42 shows the wiring connections for FSLzones on a KEY-KPZ01. Note that the resistancevalues shows are examples.KEY-KPZ01Zone 0Zone 1 2K2 EOL4K7Alarm contactsTamper contacts2K2 EOL4K7Alarm contactsTamper contacts100 OhmsFigure 42 Wiring FSL Zones on KEY-KPZ01When programming select the FSL resistor valuesfor the control unit in Installer Menu - System Options- Wired Zone Type. To select the resistor values fora wired expander use Installer Menu – DetectorsDevices – Wired Expanders - Edit Expander.If you wish to connect two or more detectors to aFSL zone, Figure 43 shows the connectionsrequired.Figure 43 Wiring Two Detectors per Zone FSL.Figure 44 shows an example of wiring doubledoors with two door contacts to one FSL zone.Each door contact is a reed switch, connected