Modifications reserved Page 28/79OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S26.3 ALARMSThe ALARMS mode is entered any time the “ALARM” button is pressed.The LCD will display a series of screens corresponding to the last 255 events, two events per screen(LEVEL 1 USER).In this mode the buttons perform the following functions:Return to HOME screen.Scrolls backward to the previous screen.Scrolls forward to the next screen.U Move forward to the following event.V Move back to the following previous event. Confirm the selection made.It is possible to view any pushbutton functional description by pushing the button for more than 3seconds.The events displayed are the standard GE events as described in the Section 6.3.1 - EVENTS (Alarmsand Messages).`Home\ AlarmALARMLEVEL 1 : USERLEVEL 2 : SERVICEV Alarms screenLEVEL 1 USERChronologically view 2 events per screenshot.LEVEL 2 SERVICEChronologically view 5 events per screenshot with servicerelated info.`Home\Alarm\UserNR = 255 05.18.2010 15.37.25C = 4404 K6 CLOSING FAILURES = 00008180NR = 254 05.15.2010 12.45.57C = 4583 COMMAND TO SYNCHRONIZES = 00008180U VScreen of user alarmsNR Number chronologically assigned to an event (Nr.255 is the more recent, Nr. 1 is the first).Date and exact hour of the moment when the eventoccurred.C Number of standard GE code of the event and anexplicit text describing the event in the selectedlanguages.S Status code of the UPS.