GE Multilin 489 Generator Management Relay 5-55 ACTUAL VALUES 5.2 A1 STATUS5Input D ALARMSTATUS: ActiveRange: see Input A ALARM STATUSInput E ALARMSTATUS: ActiveRange: see Input A ALARM STATUSInput F ALARMSTATUS: ActiveRange: see Input A ALARM STATUSInput G ALARMSTATUS: ActiveRange: see Input A ALARM STATUSTACHOMETERALARM: 3000 RPMRange: 0 to 3600 RPM. The current TachometerDigital Input value is shown hereOVERCURRENTALARM: 10.00 x FLARange: 0.00 to 20.00 × FLAThe overcurrent level is shown here.NEG. SEQ. CURRENTALARM: 15% FLARange: 0 to 100% FLA. Reflects the present negative-sequence current level.GROUND OVERCURRENTALARM: 5.00 ARange: 0.00 to 200000.00 A. Seen only if the GE HGFCT is used. Reflects the present groundcurrent level.GROUND DIRECTIONALALARM: 5.00 ARange: 0.00 to 200000.00 AUNDERVOLTAGE ALARMVab= 3245 V 78% RatedRange: 0 to 20000 V; 50 to 99% of Rated. The lowestphase-to-phase voltage value is shown hereOVERVOLTAGE ALARMVab= 4992 V 120% RatedRange: 0 to 20000 V; 101 to 150% of Rated. Thelowest phase-to-phase voltage is shown hereVOLTS/HERTZ ALARMPER UNIT V/Hz: 1.15Range: 0.00 to 2.00. The present V/Hz value is shownhere. Not seen if VT CONNECTION is None.UNDERFREQUENCYALARM: 59.4 HzRange: 0.00 to 90.00 HzReflects the present voltage frequency value.OVERFREQUENCYALARM: 60.6 HzRange: 0.00 to 90.00 HzReflects the present voltage frequency value.NEUTRAL O/V (FUND)ALARM: 0.0 VRange: 0.0 to 25000.0 V. The present fundamentalneutral voltage value is displayed here.NEUTRAL U/V (3rd)ALARM: 0.0 VRange: 0.0 to 25000.0 V. The present 3rd harmonicneutral voltage value is displayed here.REACTIVE POWER MvarALARM: +20.000Range: –2000.000 to +2000.000 MvarThe current Mvar value is shown hereREVERSE POWERALARM: –20.000 MWRange: –2000.000 to +2000.000 MWThe current MW value is shown hereLOW FORWARD POWERALARM: –20.000 MWRange: –2000.000 to +2000.000 MWThe current MW value is shown hereSTATOR RTD #1ALARM: 135°CRange: –50 to +250°C. The present RTD temperatureis shown. Reflects programmed RTD Name.OPEN SENSOR ALARM:RTD # 1 2 3 4 5 6 ...Range: RTDs 1 to 12. Reflects the RTD(s) that causedthe open sensor alarm.SHORT/LOW TEMP ALARMRTD # 7 8 9 10 11 ...Range: RTDs 1 to 12. Reflects the RTD(s) that causedthe short/low temp. alarm.MESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPEMESSAGEESCAPE