GE Multilin B30 Bus Differential System D-9APPENDIX D D.1 IEC 60870-5-104DMaximum range of values k: 1 to 32767 (2 15 – 1) APDUs, accuracy 1 APDUMaximum range of values w: 1 to 32767 APDUs, accuracy 1 APDURecommendation: w should not exceed two-thirds of k.Portnumber:RFC 2200 suite:RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in the Internetas determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual standards used in the Inter-net. The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosenby the user of this standard. Ethernet 802.3 Serial X.21 interface Other selection(s) from RFC 2200 (list below if selected)D.1.2 IEC 60870-5-104 POINTSThe IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP COMMUNICATIONS DNP /IEC104 POINT LISTS menu. Refer to the Communications section of Chapter 5 for additional details.PARAMETER VALUE REMARKSPortnumber 2404 In all cases