GE BAKER HUGHES Masoneilan SVi 1000 Quick Start Manual
© 2019 Baker Hughes, a GE company, LLC. All rights reserved. Masoneilan SVi1000 Positioner Quick Start Guide =| 21Step 1: Mounting the SVi1000This guide provides installation instructions for mounting an SVi1000 on both rotary and recipro-cating style valves. The mounting process can be broken down into the following:1. Attach the mounting bracket to the actuator.2. Install the magnetic assembly.3. Assemble the SVi1000 on the mounting bracket.CAUTION The SVi1000 cover must be in place and secured using all fourscrews during operation.NOTE Mount the SVi1000 with the conduit connection down in order tofacilitate drainage of condensate from the conduit.Necessary PrecautionsTo avoid injury or the process being affected when installing or replacing an SVi1000 positioneron a control valve, ensure that: |