CHAPTER 3: DNP COMMUNICATION DNP POINTSD90 PLUS LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE 215Figure 4: DNP user point list configuration settingsThe following settings are available for points 0 through 255.DNP Binary Input Point 0...DNP Binary Input Point 255Range: any FlexLogic operandDefault: OffThese settings represent DNP binary input points and are configured by assigning anappropriate FlexLogic operand to each. Up to 256 binary input points can be configuredfor the DNP protocol. Changes take effect when the D90 Plus is restated.DNP Analog Input Point 0...DNP Analog Input Point 255Range: any FlexAnalog parameterDefault: OffThese settings represent DNP analog input points and are configured by assigning anappropriate FlexAnalog parameter to each. Up to 256 analog input points can beconfigured for the DNP protocol. Changes take effect when the D90 Plus is restated.