Digital Energy™ gOPM_LPS_3UI_10K_20K_0US_V010.doc 13/38 Installation Guide LP 33 / 10 - 20 kVA3.2 DELIVERYWhen delivered, check carefully the package integrity and the physical conditions of the UPSequipment.In case of any damage sustained during transport, immediately inform the carrier and contact yourlocal Service Center.A detailed report of the damage is necessary for any insurance claim.NOTE !A damaged UPS must never be installed or connected to utility or battery!3.3 STORAGEThe equipment is carefully packed fortransport and storage so that it is in a perfectcondition when eventually installed.Never leave an UPS outside the building anddo not store the UPS one on top of the other.It is recommended to store the UPS in itsoriginal package in a dry, dust free roomand far away from chemical substances,with temperature not exceeding -13°F to131°F (-25°C to 55°C).3.3.1 Storage of the UPSSome important functions of the UPS, such as the customized functions, are defined byparameters stored in a RAM memory.The RAM is supplied by a small backup battery located on the Control Unit board.If the storage time of the UPS exceeds 1 year, these functions should be verified by anauthorized Service Center before putting the UPS into operation.NOTE !In case of storage of the UPS pay attention to: FRAGILESENSITIVETO DAMPNESS TO HEATSENSITIVETO FROSTSENSITIVE