g GEOPM_SGS_ISG_10K_40K_0US_V010.doc 12/45 Installation Guide SG Series 10, 20, 30 & 40 kVA3.2 DELIVERYWhen delivered, inspect the package integrity and the physical conditions of thecabinets carefully.In case of any damage sustained during transport, immediately inform the carrier and contactyour local Service Center.A detailed report of the damage is necessary for any insurance claim.A DAMAGED UPS MUST NEVER BE INSTALLED OR CONNECTED TOUTILITY OR BATTERY!3.3 STORAGE3.3.1 Storage of the UPSThe UPS is carefully packed for transport and storage so that it is in perfect condition wheninstalled.Never leave a UPS outside the building and don’t store other packages on the top of theUPS.It is advisable to store the UPS in its original package in a dry, dust-free room, away fromchemical substances, and with a temperature range not exceeding -13°F (-25°C) to 131°F(55°C).Some important functions of the UPS, such as the customized functions, are defined byparameters stored in a RAM memory.A small backup battery located on the Control Unit board supplies the RAM.If the storage time of the UPS exceeds 1 year, these functions should be verified by anauthorized Service Center before putting the UPS into operation.3.3.2 Storage of batteryWhen the delivery includes a maintenance free battery, keep in mind that they are subject toself-discharge and therefore you must recharge the battery.The storage time without battery recharge depends on the temperature of the storage site.The optimal temperature for battery storage is 68°F (20°C) to 77°F (25°C).Recharge stored maintenance free battery every:6 months when the storage temperature is 68°F (20°C)3 months when the storage temperature is 86°F (30°C)2 months when the storage temperature is 95°F (35°C)